Selection and spacing requirements for smoke detectors in hotel guest rooms

Fire protection engineeringUpdated 2026-05-13

I am fire protection expert Alexander Li. The selection and spacing of smoke detectors in hotel guest rooms is one of the core elements in the design of automatic fire alarm syste…

Selection and spacing requirements for smoke detectors in hotel guest rooms

I am fire protection expert Alexander Li. The selection and spacing of smoke detectors in hotel guest rooms is one of the core elements in the design of automatic fire alarm systems, directly affecting the reliability of early fire detection and the life safety of guests. Based on my years of engineering experience, this issue is often overlooked during the design phase, but in actual operation, false alarms or blind spots can lead to serious consequences. The following analysis is developed from three aspects: standard basis, selection key points, and spacing requirements.

Selection Requirements


According to Article 5.2.2 of the Code for Design of Automatic Fire Alarm Systems (GB 50116-2013), guest rooms belong to locations "where smoldering fires may occur or where a large amount of smoke and a small amount of heat are produced in the initial stage of a fire," and point-type smoke detectors should be preferentially selected. For specific selection:

Spacing Requirements


Spacing shall follow Articles 6.2.2 to 6.2.5 of GB 50116-2013 and be combined with the actual area and shape of the guest room:

Actual Engineering Case


In a city business hotel project, the guest room area was 35㎡, the ceiling height was 2.8m, and a central air-conditioning return air outlet was installed. In the initial design, only one photoelectric smoke detector was arranged at the center of the room, but acceptance testing found that smoke diffused slowly at 1.2m from the return air outlet, and the detector response time exceeded the limit. The adjustment was as follows: the detector was moved to 2.0m from the return air outlet, and an auxiliary detector was added above the wardrobe (a smoldering risk area). After rectification, the response time dropped from 45 seconds to 18 seconds, meeting the requirements of Article 3.2.1 of GB 50116-2013.

Concluding Summary


Photoelectric smoke detectors should be selected for hotel guest rooms, preferably arranged at the center of the room or away from air-conditioning outlets. The spacing must ensure a protection radius ≤5.8m and a distance from air outlets ≥1.5m, with consideration given to the influence of beams and humidity. The above are reference opinions. The actual project situation still needs to be further comprehensively evaluated and implemented in combination with specific operating conditions, site conditions, and other factors.