Classification of protected objects and system selection for hotel automatic fire alarm systems

Fire protection engineeringUpdated 2026-05-13

I am fire protection expert Alexander Li. In the design of hotel automatic fire alarm systems, protection object classification and system selection are the core foundation determ…

Classification of protected objects and system selection for hotel automatic fire alarm systems

I am fire protection expert Alexander Li. In the design of hotel automatic fire alarm systems, protection object classification and system selection are the core foundation determining the effectiveness of the entire fire protection system—they directly affect detector layout, linkage control logic, power supply configuration, and later operation and maintenance costs. According to the Code for Design of Automatic Fire Alarm Systems (GB50116-2013), hotels, as places with dense occupancy, must strictly follow the code in their classification and selection, and be optimized in combination with actual operational needs.

Protection Object Classification


According to Article 3.1.1 of GB50116-2013, protection objects of automatic fire alarm systems shall be classified as Level 1, Level 2, and Level 3 according to building height, nature of use, fire hazard, and evacuation difficulty. Hotels generally belong to Level 1 protection objects, with specific basis as follows:
Practical engineering experience: I once participated in a 50-storey luxury hotel project (height 180 m), classified as a Level 1 protection object according to the code. During system selection, we considered not only building height but also high-risk areas within the hotel such as dining areas, kitchens, and boiler rooms, to ensure detector density and linkage control met the code.

System Selection


According to Article 3.2.1 of GB50116-2013, system selection is divided into regional alarm systems, centralized alarm systems, and control center alarm systems. Hotels are recommended to adopt centralized alarm systems or control center alarm systems, as follows:
Key points for selection:
1. Linkage requirements: Hotels need linkage with sprinklers, smoke control and exhaust, fire shutters, and other equipment. According to Article 4.1.1 of GB50116, a centralized alarm system must be equipped with a linkage controller.
2. Power supply configuration: Article 10.1.1 of GB50116 requires the main power supply of the system to use fire protection power, and the backup power supply to continuously operate for no less than 30 minutes (no less than 60 minutes for super high-rise buildings). In hotels, I have encountered cases of frequent power outages, so I recommend using UPS + diesel generator dual backup.
3. Detector selection: Use smoke detectors in guest rooms (to avoid false alarms); use heat detectors in kitchens (to prevent oil fume interference). Referring to Article 5.2.1, the installation spacing of smoke detectors shall not exceed 15 m.

Practical case:
In 2019, I participated in the fire protection system design of a five-star hotel (48 storeys, height 160 m). The original design was determined as a centralized alarm system, but during review it was found that the hotel included an underground garage, boiler room, and banquet hall (area exceeding 2,000 ㎡). According to Article 3.2.3 of GB50116, we upgraded it to a control center alarm system: the main control room was set on the first floor, and the auxiliary control room was set in the fire pump room. The system adopted intelligent detectors (such as Honeywell Notifier series), with linkage to fans, water pumps, and sound and light alarms. During acceptance, through simulated fire testing, the linkage response time was less than 5 seconds, meeting the code requirements.

Concluding Summary


Hotel automatic fire alarm systems should be classified as Level 1 or Level 2 protection objects based on building height and risk level, and are recommended to adopt centralized alarm systems (high-rise) or control center alarm systems (super high-rise/complex), strictly following the linkage control, power supply, and detector selection requirements of GB50116-2013 to ensure personnel safety and equipment reliability.

The above are reference opinions. The actual project situation still needs further comprehensive evaluation and implementation in combination with specific working conditions, site conditions, and other factors.

Still have a specific question? Ask a MEP expert

12 hotel MEP experts online, answers cite standard clauses you can verify.

Ask free →

Engineering reference only — verify against project conditions and the latest codes.