Classification of protected objects and system selection for hotel automatic fire alarm systems
I am fire protection expert Alexander Li. In the design of hotel automatic fire alarm systems, protection object classification and system selection are the core foundation determining the effectiveness of the entire fire protection system—they directly affect detector layout, linkage control logic, power supply configuration, and later operation and maintenance costs. According to the Code for Design of Automatic Fire Alarm Systems (GB50116-2013), hotels, as places with dense occupancy, must strictly follow the code in their classification and selection, and be optimized in combination with actual operational needs.
Protection Object Classification
According to Article 3.1.1 of GB50116-2013, protection objects of automatic fire alarm systems shall be classified as Level 1, Level 2, and Level 3 according to building height, nature of use, fire hazard, and evacuation difficulty. Hotels generally belong to Level 1 protection objects, with specific basis as follows:
- Level 1 protection objects: Super high-rise hotels with building height exceeding 100 m, or Class I high-rise public buildings (such as hotels with more than 100 guest rooms). For example, Article 3.1.1 explicitly states: "Class I high-rise public buildings shall be equipped with automatic fire alarm systems, and the system shall be Level 1."
- Level 2 protection objects: Class II high-rise hotels with building height not exceeding 54 m, or multi-storey hotels not exceeding 24 m (such as economy hotels with fewer than 100 guest rooms). However, according to Article 3.1.3, if the hotel contains singing, dancing, entertainment, and amusement venues (such as KTVs and banquet halls), it must be upgraded to Level 1.
- Level 3 protection objects: Only applicable to small, low-risk premises (such as rural homestays), but hotels are almost never applicable.
System Selection
According to Article 3.2.1 of GB50116-2013, system selection is divided into regional alarm systems, centralized alarm systems, and control center alarm systems. Hotels are recommended to adopt centralized alarm systems or control center alarm systems, as follows:
- Centralized alarm system: Applicable to high-rise hotels that are Level 1 protection objects (such as height exceeding 50 m). The system consists of fire detectors, manual alarm call points, regional displays, and a centralized controller. For example, Article 3.2.2 requires: "A centralized alarm system shall be provided with a fire control room, and the controller shall have linkage control functions." In hotels, this enables zoned management of guest rooms, corridors, and public areas.
- Control center alarm system: Applicable to super high-rise hotels (height exceeding 100 m) or large hotel complexes (containing multiple functional blocks). Article 3.2.3 stipulates: "A control center alarm system requires two or more fire control rooms, with the main control room responsible for global linkage." I once was responsible for a complex project containing a hotel, shopping mall, and office building, which adopted this system, connecting each control room via a fiber-optic ring network to ensure emergency response speed.
1. Linkage requirements: Hotels need linkage with sprinklers, smoke control and exhaust, fire shutters, and other equipment. According to Article 4.1.1 of GB50116, a centralized alarm system must be equipped with a linkage controller.
2. Power supply configuration: Article 10.1.1 of GB50116 requires the main power supply of the system to use fire protection power, and the backup power supply to continuously operate for no less than 30 minutes (no less than 60 minutes for super high-rise buildings). In hotels, I have encountered cases of frequent power outages, so I recommend using UPS + diesel generator dual backup.
3. Detector selection: Use smoke detectors in guest rooms (to avoid false alarms); use heat detectors in kitchens (to prevent oil fume interference). Referring to Article 5.2.1, the installation spacing of smoke detectors shall not exceed 15 m.
Practical case:
In 2019, I participated in the fire protection system design of a five-star hotel (48 storeys, height 160 m). The original design was determined as a centralized alarm system, but during review it was found that the hotel included an underground garage, boiler room, and banquet hall (area exceeding 2,000 ㎡). According to Article 3.2.3 of GB50116, we upgraded it to a control center alarm system: the main control room was set on the first floor, and the auxiliary control room was set in the fire pump room. The system adopted intelligent detectors (such as Honeywell Notifier series), with linkage to fans, water pumps, and sound and light alarms. During acceptance, through simulated fire testing, the linkage response time was less than 5 seconds, meeting the code requirements.
Concluding Summary
Hotel automatic fire alarm systems should be classified as Level 1 or Level 2 protection objects based on building height and risk level, and are recommended to adopt centralized alarm systems (high-rise) or control center alarm systems (super high-rise/complex), strictly following the linkage control, power supply, and detector selection requirements of GB50116-2013 to ensure personnel safety and equipment reliability.
The above are reference opinions. The actual project situation still needs further comprehensive evaluation and implementation in combination with specific working conditions, site conditions, and other factors.