Height and capacity requirements for hotel fire water tanks
I am Daniel Wang, a water supply and drainage specialist. In hotel fire protection system design, the installation height and volume of the fire water tank are key parameters for ensuring effective initial fire suppression, and they directly affect system reliability and personnel safety. Below, I will combine the Technical Code for Fire Protection Water Supply and Hydrant Systems (GB 50974-2014) and years of engineering experience to analyze these two core requirements in detail.
1. Installation height requirements for the fire water tank
According to Article 5.2.2 of GB 50974-2014, the installation height of the high-level fire water tank shall ensure the static pressure at the most unfavorable hydrant. For hotel buildings:
- Class I high-rise public buildings (such as star-rated hotels ≥50 m): shall not be less than 0.10 MPa (i.e., 10 m water column); when the building height exceeds 100 m, shall not be less than 0.15 MPa.
- Class II high-rise public buildings (such as hotels <50 m): shall not be less than 0.07 MPa.
- Multi-story hotels: shall not be less than 0.07 MPa.
Engineering case: An international hotel in Shenzhen (120 m high) initially had a tank height of only 8 m, which did not meet the 0.15 MPa requirement. By optimizing the tank position to the highest point of the roof (increasing the height by 2 m) and configuring a pressure-maintaining pump (flow rate 4 L/s, head 0.2 MPa), the system ultimately passed acceptance, and in the fire simulation test, the static pressure remained stable at 0.18 MPa.
2. Volume requirements for the fire water tank
According to Article 5.2.1 of GB 50974-2014, the effective volume of the high-level fire water tank shall meet the fire water demand for initial fire suppression:
- Class I high-rise public buildings (such as hotels ≥50 m): ≥36 m³; when the building height exceeds 100 m, ≥50 m³; when it exceeds 150 m, ≥100 m³.
- Class II high-rise public buildings (such as hotels <50 m): ≥18 m³.
- Multi-story hotels: ≥18 m³ (but shall be calculated in conjunction with the indoor fire water demand).
Engineering case: A business hotel in Beijing (height 60 m) originally had a designed tank volume of 30 m³. During review, it was found that according to the code, 36 m³ was required, and the sprinkler system did not have a separate pressure-maintaining unit. We adjusted it to a stainless steel assembled water tank (36 m³) and added a sprinkler pressure-maintaining pump, which both met the code and saved structural reinforcement costs. After operation, in a simulated fire test, the water tank supplied water continuously for 12 minutes, fully covering initial fire suppression.
3. Comprehensive precautions
- Tank material: SUS304 stainless steel is recommended to avoid corrosion and contamination. Article 5.2.3 of GB 50974-2014 requires that the tank material be corrosion-resistant.
- Freeze protection measures: Tank rooms in northern hotels need insulation, with the temperature not lower than 5℃; otherwise, pipes may freeze and affect water supply.
- Water level control: Install liquid level sensors and overflow pipes to ensure automatic replenishment and prevent drying out.
The above are reference opinions. The actual project conditions still need to be further comprehensively evaluated and implemented in combination with specific operating conditions, site conditions, and other factors.