Selection criteria and design key points for hotel siphonic and gravity rainwater systems

PlumbingUpdated 2026-05-13

I am Daniel Wang, a water supply and drainage specialist. The choice between a siphonic rainwater system and a gravity rainwater system is a core decision in hotel roof rainwater …

Selection criteria and design key points for hotel siphonic and gravity rainwater systems

I am Daniel Wang, a water supply and drainage specialist. The choice between a siphonic rainwater system and a gravity rainwater system is a core decision in hotel roof rainwater drainage design, directly affecting building safety, drainage efficiency and later operation and maintenance costs. Based on GB50015-2019 "Standard for Design of Building Water Supply and Drainage" and years of hotel project experience, I will analyze in detail the selection conditions and design key points.

Selection Condition Analysis

1. Roof Area and Catchment Conditions

2. Building Space and Aesthetic Requirements
3. Climate and Rainfall Intensity

Design Key Points

1. Gravity System

2. Siphonic System

Practical Engineering Cases

A resort hotel in Hangzhou (guest room area roof 2000㎡) chose a gravity system. Design key points: gutter slope 0.8%, outlet spacing 10m, 4 risers (DN150). No water ponding occurred in 5 years of operation, but fallen leaves in the gutters need regular cleaning during the rainy season.
An international hotel in Beijing (banquet hall roof 6000㎡) adopted a siphonic system. Design return period 50 years, 8 siphonic outlets (each draining 750㎡), 2 risers (DN200). During construction, because the gutter depth was insufficient (only 0.2m), it was adjusted to 0.35m and anti-vortex plates were added. After 3 years of operation, drainage efficiency is high, but the sealing of the siphonic outlets needs to be checked annually.

Concluding Summary


Hotel siphonic rainwater systems are suitable for large-area, high-aesthetic-requirement or space-constrained scenarios, but require precise hydraulic calculation and professional construction; gravity systems are simpler and more reliable, suitable for small-area or low-requirement areas. Design must strictly follow the clauses of GB50015, combine local climate and building conditions, and ensure the overflow system is independent and reliable.
The above are reference opinions. The actual project situation still needs further comprehensive evaluation and implementation in combination with specific working conditions, site conditions and other factors.