How is the makeup water volume for cooling towers calculated? What are the water quality treatment standards? How can Legionella growth be prevented?

HVACUpdated 2026-05-13

I am an HVAC expert. The calculation of cooling tower makeup water, water quality treatment standards, and Legionella prevention and control are key aspects of HVAC system design …

How is the makeup water volume for cooling towers calculated? What are the water quality treatment standards? How can Legionella growth be prevented?

I am an HVAC expert. The calculation of cooling tower makeup water, water quality treatment standards, and Legionella prevention and control are key aspects of HVAC system design and O&M, directly affecting system energy efficiency, equipment lifespan, and public health safety. In accordance with the Code for Design of Heating Ventilation and Air Conditioning for Civil Buildings (GB 50736-2012) and the Code for Design of Industrial Circulating Cooling Water Treatment (GB 50050-2017), and drawing on years of engineering experience, I provide the following detailed analysis:

1. Cooling Tower Makeup Water Calculation


Cooling tower makeup water must comprehensively account for evaporation loss, wind drift loss, blowdown loss, and leakage loss. According to GB 50736-2012 Clause 8.6.6 and practical experience, the following method is recommended:

Total makeup water = evaporation loss + wind drift loss + blowdown loss + leakage loss. In actual engineering, it is often estimated at 1.5%–2.5% of the circulating water volume. For example, for a hotel project with a circulating water volume of 800 m³/h, a temperature difference of 5℃, and 4 cycles of concentration, the makeup water is approximately 16–20 m³/h.

2. Water Quality Treatment Standards


According to GB 50050-2017 Clause 3.1.1, circulating cooling water quality shall meet the following key indicators (taking an open system as an example):
Treatment measures: A fully automatic chemical dosing unit (corrosion and scale inhibitor, biocide) and a side-stream filtration system (e.g., sand filtration or self-cleaning filters) are required, with regular water quality testing and adjustment of chemical dosage. In an actual case, a commercial complex failed to control the cycles of concentration, causing scaling of the fill and a 30% drop in heat exchange efficiency, which was resolved by installing automatic blowdown valves and a chemical dosing system.

3. Legionella Growth Prevention and Control


Legionella is a common pathogen in cooling towers; its growth conditions are a water temperature of 25–45℃, stagnant water zones, and the presence of biofilm. According to the Hygienic Specification for Centralized Air Conditioning Ventilation Systems in Public Places (WS 394-2012) and the US ASHRAE 188-2018 standard, prevention and control measures include:

Engineering case: A five-star hotel once failed to disinfect its cooling tower regularly, resulting in a Legionella detection value of 500 CFU/L and complaints of respiratory infections from guests. An automatic chlorination system (maintaining free chlorine at 1.0 mg/L) combined with monthly cleaning was subsequently adopted, and the detection value dropped to 0 CFU/L.

Summary


Cooling tower makeup water must be calculated comprehensively based on evaporation, wind drift, blowdown, and leakage losses, typically 1.5%–2.5% of the circulating water volume; water quality treatment must strictly follow the GB 50050-2017 indicators, combined with chemical dosing and side-stream filtration systems; Legionella prevention and control must be achieved through water temperature control, periodic disinfection, and system design optimization. The above measures can effectively ensure stable system operation and public health safety.

The above are reference opinions. The actual project situation still needs further comprehensive evaluation and implementation in combination with specific operating conditions, site conditions, and other factors.