What are the selection steps and variable-frequency control strategy for air-conditioning chilled water pumps and cooling water pumps?

HVACUpdated 2026-05-13

I am an HVAC expert with many years of experience in HVAC system design and optimization, and I know well that pump selection and variable frequency control strategy are the core …

What are the selection steps and variable-frequency control strategy for air-conditioning chilled water pumps and cooling water pumps?

I am an HVAC expert with many years of experience in HVAC system design and optimization, and I know well that pump selection and variable-frequency control strategy are the core of the energy efficiency and stability of central air-conditioning systems. Improper pump selection will lead to a surge in system energy consumption, hydraulic imbalance, and even equipment damage; if the variable-frequency control strategy is unreasonable, it cannot realize energy-saving potential and may even cause oscillation or inefficient operation. The following is a detailed analysis based on standards and engineering experience.

I. Selection steps for chilled water pumps and cooling water pumps

1. Clarify system design parameters
According to Article 8.2.1 of GB 50736-2012 "Design Code for Heating Ventilation and Air Conditioning of Civil Buildings," the design flow of pumps shall be calculated based on cooling load and supply-return water temperature difference:

Empirical note: In actual projects, the simultaneity factor (usually 0.7~0.9) and pipeline heat loss (about 5%~10%) need to be considered to avoid oversized selection.

2. Calculate system resistance
According to Article 9.6.3 of GB 50019-2015 "Design Code for Heating Ventilation and Air Conditioning of Industrial Buildings," the pump head shall overcome the total resistance of the most unfavorable loop, including:

Actual case: In a five-star hotel project, the total resistance of the most unfavorable chilled water loop was calculated by hydraulic calculation as 28mH₂O, but the designer initially selected a head of 35m (including a 10% safety factor), causing the pump operating point to deviate from the high-efficiency zone. After optimization to 30m, annual power savings were about 12%.

3. Determine pump model and number

II. Variable-frequency control strategy

1. Control objectives and principles
The core of variable-frequency control is to adjust pump speed to match real-time load, following the affinity laws: flow is proportional to speed, head is proportional to the square of speed, and power is proportional to the cube of speed. Article 8.5.9 of GB 50736 explicitly requires that air-conditioning water systems should adopt variable-frequency speed control.

2. Chilled water pump variable-frequency strategy

3. Cooling water pump variable-frequency strategy
4. Precautions

III. Actual engineering case

Case: A super high-rise office building (building area 120,000 m²)

Summary

The selection of chilled water pumps and cooling water pumps must strictly follow GB 50736 and GB 50019, determine flow and head in combination with hydraulic calculation, and reasonably configure the number of pumps; variable-frequency control strategies should give priority to differential pressure or temperature difference control, and attention must be paid to safety limits and multi-pump coordination. Through optimized selection and control, system energy efficiency can be significantly improved and equipment life extended.

The above are reference opinions. The actual situation of the project still needs to be comprehensively evaluated and implemented in combination with specific operating conditions, site conditions, and other factors.