How should the cool storage and heat storage scheme for a hotel air-conditioning system be selected? What are the respective advantages of ice storage and chilled water storage?

HVACUpdated 2026-05-13

I am an HVAC expert. The selection of cool storage and heat storage schemes for hotel air conditioning systems is a key part of the design, directly affecting initial investment, …

How should the cool storage and heat storage scheme for a hotel air-conditioning system be selected? What are the respective advantages of ice storage and chilled water storage?

I am an HVAC expert. The selection of cool storage and heat storage schemes for hotel air-conditioning systems is a key part of the design, directly affecting initial investment, operating costs, plant room floor area, and the hotel's flexibility in responding to peak-valley electricity pricing and load fluctuations. According to Section 8.7 of the Code for Design of Heating Ventilation and Air Conditioning of Civil Buildings GB 50736-2012 and the Technical Specification for Cool Storage Air-Conditioning Engineering JGJ 158-2008, the design of energy storage systems must comprehensively consider the local electricity pricing policy, building load characteristics, site conditions and economics. Below I analyse in detail the scheme selection and advantages of ice storage and chilled water storage.

Scheme Selection Principles


Hotel loads are characterised by large day-night fluctuations, a high proportion of cooling load in summer, and the continued need for cooling in some areas (such as guest rooms) at night. When selecting a cool storage scheme, the following steps should be followed:
1. Load analysis: According to Article 8.7.1 of GB 50736-2012, the hourly cooling load on the design day should be calculated to determine the cool storage capacity. For example, a five-star hotel has a peak cooling load of about 5000 kW and a night-time (23:00-07:00) cooling load of about 1500 kW; the cool storage system needs to balance the peak-valley difference.
2. Electricity pricing policy: Taking advantage of the peak-valley price difference (e.g., a peak-valley ratio of 3:1 or above), priority should be given to schemes with a high cool storage ratio. Ice storage has a high cool storage density and is suitable for projects with limited space; chilled water storage has a low initial investment and is suitable where large water tanks are available.
3. Site and equipment: Ice storage requires consideration of ice tanks and a glycol system, while chilled water storage requires a large-volume chilled water storage tank. Hotel basements are usually tight, so ice storage is more common.

Advantages of Ice Storage


Ice storage uses off-peak electricity at night to make ice and melts the ice during the day to supply cooling; the cool storage density is about 50-60 kWh/m³ (chilled water storage is only 7-12 kWh/m³). According to Article 4.2.2 of the Technical Specification for Cool Storage Air-Conditioning Engineering JGJ 158-2008, ice storage systems may adopt an upstream series or parallel arrangement of the chiller.

Advantages of Chilled Water Storage


Chilled water storage uses the sensible heat of water (temperature difference 6-10℃); the cool storage density is low, but the system is simple. According to Article 8.7.3 of GB 50736-2012, chilled water storage may adopt a naturally stratified or labyrinth design.

Scheme Comparison and Selection Recommendations


| Parameter | Ice Storage | Chilled Water Storage |
|--------------|---------------------------|---------------------------|
| Cool storage density | 50-60 kWh/m³ | 7-12 kWh/m³ |
| Initial investment | Higher (equipment + glycol system) | Lower (tank + simple equipment) |
| Floor area | Small (about 1/5) | Large (requires a large tank) |
| Operating efficiency | Low ice-making efficiency (COP about 3.5) | High storage efficiency (COP about 5.0) |
| Applicable scenarios | Limited space, large peak-valley price difference | Idle space available, initial-investment sensitive |

Selection recommendations:

Concluding Summary


The selection of cool storage and heat storage schemes for hotel air-conditioning systems should be based on load characteristics, electricity pricing policy and site conditions: ice storage is suitable for projects with limited space and a large peak-valley price difference, and can significantly save plant room area and support low-temperature air supply; chilled water storage is suitable for projects that are initial-investment sensitive and have idle water tanks, with a simple system and convenient maintenance. In actual design, Section 8.7 of GB 50736-2012 and JGJ 158-2008 must be strictly followed, and the optimal scheme determined through technical and economic comparison.
The above are reference opinions. The actual situation of the project still needs to be further evaluated and implemented in combination with specific operating conditions, site conditions and other factors.