Common Construction Process Issues and Solutions

Construction workmanship Updated 2026-04-25 0 views

Summarize common issues in hotel MEP construction processes, covering cause analysis and solutions for typical problems in the construction, commissioning, and operation stages of HVAC, plumbing, electrical, a…

1. Common HVAC System Issues

Common HVAC construction issues: Excessive air duct leakage — Causes: poorly sealed seams, unsealed flange gaskets, unsealed reinforcement holes. Solution: Strengthen self-inspection during fabrication; after installation, perform light-leak testing for low-pressure ducts or leakage rate testing for medium/high-pressure ducts. Air-conditioning water pipe hydraulic imbalance — large terminal temperature differential, near-end cold and far-end hot — Causes: no balancing valves installed or balancing valves not commissioned. Solution: Install static/dynamic balancing valves and perform hydraulic balancing commissioning so that flow deviation of each branch is ≤15%. Condensate pipe blockage causing water leakage — Causes: insufficient slope, no vent provided in trap, pipe with no slope.

2. Common Plumbing and Drainage System Issues

Common plumbing and drainage system issues: Poor drainage and backflow at sanitary fixtures — Causes: drainage pipe slope less than 0.5%, pipe blockage, poor venting system. Solution: Ensure drainage pipe slope ≥0.5% (except vertical stacks); use oblique wyes for horizontal pipe connections; provide cleanouts on each floor at 1 m above floor; vent stack extending through roof shall be no less than 1/2 the diameter of the drainage stack. Low terminal temperature in hot water system — Causes: circulation pipeline does not form a loop, return pipe design unreasonable, circulation pump undersized. Solution: Adopt reverse-return hot water circulation system; return pipe diameter no less than 1/2 the supply pipe diameter; circulation pump head calculated based on the most unfavorable loop.

3. Common Electrical System Issues

Common electrical system issues: Frequent tripping of residual current devices — Causes: poor line insulation with insulation resistance less than 0.5 MΩ, equipment leakage, MCCB undersized so normal leakage current plus equipment starting current causes tripping. Solution: Troubleshoot line insulation using a megohmmeter to test circuit by circuit; check suspect equipment such as electric water heaters and kitchen appliances. Cable overheating — Causes: insufficient ampacity, undersized design or actual load exceeding rating, poor heat dissipation, high joint resistance. Solution: Calculate actual load current, check joint quality with infrared thermal imaging, add heat dissipation measures or replace with larger cross-section cable. Excessive neutral-to-ground voltage greater than 2V — Causes: three-phase imbalance, undersized neutral conductor, poor grounding.

4. Construction Commissioning and Cross-Operation Issues

Common construction commissioning issues: Chaotic commissioning sequence — failing to follow the principle of single equipment first then system, no-load first then loaded — making problem localization difficult. Solution: Develop a detailed commissioning plan specifying commissioning steps and acceptance criteria. Uncalibrated commissioning instruments — e.g., large deviations in flow meters and thermometers — leading to inaccurate commissioning data. Solution: Send all instruments for inspection and calibration before commissioning, valid for 1 year; perform on-site comparison among multiple meters. Excessive noise and vibration — equipment foundations without vibration isolation or with failed vibration isolation. Solution: Check vibration isolator quality before equipment installation; measure vibration after installation of important equipment, ≤4 mm/s.